1.Features:
① The printed circuit board is directly welded and installed, and the appearance is beautiful;
② Compact, high precision; fully enclosed, good mechanical and environmental resistance, strong voltage isolation capability, safe and reliable.
2.Ambient Conditions:
① Ambient temperature: -55℃~+85℃;
② Relative humidity: ≤90% at 40℃;
③ Atmospheric pressure: 860~1060mbar(about 650~800mmHg).
3.Operating Frequency Range: 2kHz~200kHz;
4.Insulation Thermal Class: Class B (130℃)
5.Safety Features:
① Insulation resistance: >1000MΩ in normal condition;
② Insulation withstand voltages: 2.5KV 50Hz/1min;
③ Fire retardancy: In conformity with UL94-V0.
6. Outline Drawing and Installation Dimension
Coil Diagram: ( tolerance ± 0.3mm )
① Outline drawing and installation dimensions are shown in Figure 1:
② The coil diagram is shown in Figure 2:
Fig 1
7. Performance Parameters:
Obtain the sampling voltage directly with the resistance method as shown in Figure 3 . The performance parameters are shown in the table below:
Model | Rated Input Current | Rated Output Current | Rated Sampling Resistance R L | Rated Sampling Voltage | Non- Linearity | Linear Range |
TA0510-01 | 10A | 0.2A | 2Ω | 0.4V | ≤2% | ≥2 times of the rated value |
TA0510-02 | 10A | 0.1A | 8Ω | 0.8V | ≤2% | ≥2 times of the rated value |
8.Attention:
① Connect the primary winding of the current transformer in series with the measured current loop. Operate the secondary winding in a near short-circuit mode.
② Do not allow the secondary winding of the current transformer to be open-circuited. Do not install any fuse on the secondary winding.